Industrial cybersecurity

Industrial OT/ICS/SCADA security: Clavister and Cyber Praxis

Protect your critical infrastructure and industrial systems with European cybersecurity technology developed in Sweden and supported by the Belgian experts of Cyber Praxis.

Cyber Praxis is a Clavister partner. As an independent consulting and expert firm, we analyse your industrial risks, design the architecture, then install, configure and audit the Clavister firewalls. No production environment is changed without an impact analysis and a rollback plan.

Clavister Partner

A European sovereign firewall, developed in Sweden

Clavister is a Swedish cybersecurity vendor founded in 1997 and headquartered in Örnsköldsvik. Its NetWall firewalls are designed and developed in Sweden and can be deployed and managed entirely on your own sites.

  • European vendor

    Swedish company listed on Nasdaq Stockholm, ISO/IEC 27001 certified since 2025.

  • Technology developed in Sweden

    NetWall firewalls are designed and developed in Sweden, for critical infrastructure and demanding industrial environments.

  • Fully on-premises deployment

    Firewalls, central management (InControl or InCenter) and logs can stay on your own servers.

  • Less dependence on the cloud

    Clavister's cloud services, such as InCenter Cloud or zero-touch deployment, remain optional.

What we distinguish for every project

Sovereignty is checked point by point: no technology guarantees it on its own.

PointClavister (official documentation)What we check with you
Vendor originSwedish company, headquartered in ÖrnsköldsvikOwnership, subcontractors and applicable law
Place of developmentNetWall range designed and developed in SwedencOS Core version chosen and support period
Management consolesInControl (Windows server) or InCenter installed on your premises; InCenter is also available as a cloud serviceOn-premises or cloud, configuration backups
Logs and telemetrySent to your syslog servers, your SIEM or an on-premises InCenterOutbound flows actually needed and their destination
UpdatesSubscription features (application control, intrusion prevention) are updated by ClavisterDelivering updates to an isolated network
Optional cloud servicesInCenter Cloud, zero-touch deploymentWhat is enabled, disabled or controlled
Contractual guaranteesThe vendor's licence, support and data processing termsReview before signature, with a certified DPO

The environments we protect

Systems built to last for decades, often without authentication or encryption, and now connected to the corporate network.

OT (Operational Technology)
The technology that controls and monitors physical processes.
ICS (Industrial Control Systems)
Industrial control systems, from the controller to the supervision station.
SCADA
Supervisory control and data acquisition for remote sites: electricity, water, transport.
DCS (Distributed Control Systems)
Control of continuous processes in chemicals, pharmaceuticals or energy.
PLC (Programmable Logic Controllers)
The controllers that drive machines and production lines.
RTU (Remote Terminal Units)
The units that connect field equipment to SCADA.
HMI (Human-Machine Interfaces)
The operators' control screens.
IIoT (Industrial Internet of Things)
Connected industrial sensors and devices.
Legacy systems
Older equipment that cannot be updated without stopping production.
BMS (Building Management Systems)
Technical building management: heating, ventilation, access, energy.

The security functions that matter in industrial environments

Documented functions of cOS Core, the operating system of Clavister NetWall firewalls. Some depend on the model or on a subscription.

  • IT/OT segmentation, zones and conduits

    Filtering policies between zones only allow the flows that are needed and limit lateral movement.

  • Industrial DMZ

    A buffer zone between IT and OT for data exchange, updates and remote access, with no direct link between the two networks.

  • Industrial protocol recognition

    Application control identifies Modbus, IEC 60870-5-104, OPC UA, EtherNet/IP and CIP, PROFINET, IEC 61850 (GOOSE, MMS), BACnet and S7, among others, to allow or block each protocol between zones (subscription feature).

  • Intrusion prevention

    The IDP engine detects and blocks attempts to exploit vulnerabilities over the network.

  • Transparent operation

    Transparent mode inserts the firewall without changing the addressing of the existing network. It is not available in a high availability cluster.

  • VPN and supplier remote access

    IPsec tunnels and the OneConnect VPN client; maintenance providers' access is limited, logged and goes through the DMZ.

  • Central management

    Configurations, versions and licences managed from InControl or InCenter, installed on your own servers if you wish.

  • High availability

    Two identical firewalls in an active/passive cluster, with connection state replication.

  • Hardware bypass, depending on the model

    On the NetWall 200R, two ports pass traffic without any inspection during a power cut: a continuity choice to be weighed against security.

  • Logging and SOC integration

    Time-stamped events sent to your syslog servers, your SIEM or a SOC, to link OT activity with the rest of the information system.

Protocols listed: cOS Core 15.00 application control signature database, consulted in November 2026. DNP3 is not in it: for a DNP3 network, we check feasibility with Clavister before any commitment. Recognising a protocol is not the same as analysing every command: the study states what is filtered, and at which level.

Reference architecture

A conceptual layered architecture, inspired by the Purdue model and the IEC 62443 zones and conduits, to be adapted to your requirements after a risk analysis.

  1. External networks Internet / WAN External access, remote sites, suppliers
  2. Internet boundary Perimeter firewall Protects the company's information system
  3. Levels 4 and 5: enterprise IT network Office tools, email, business systems
  4. IT – DMZ conduit Clavister firewall Only authorised flows reach the DMZ
  5. Level 3.5: IT/OT exchanges Industrial DMZ Historian, jump servers, update repository
  6. DMZ – OT conduit Clavister OT firewall Control of industrial protocols towards OT
  7. Level 3: operations Industrial network Supervision servers and engineering workstations
  8. Levels 1 and 2: supervision and control SCADA, HMI, PLC, RTU Operation, controllers and remote units
  9. Level 0: physical process Production equipment Sensors, actuators, machines
Indicative diagram: the number of zones, the placement of firewalls and the authorised flows depend on your risk analysis and operating constraints.

Clavister NetWall 200R, the firewall for the industrial cabinet

The NetWall 200R Series is the ruggedised model of the NetWall range: DIN rail housing, wide temperature range and DC power, for installation as close as possible to the equipment.

FeatureNetWall 200R Series
Form factorDIN rail housing, 150 × 66 × 127 mm, 1.5 kg
Operating temperature−40 °C to +70 °C
Humidity10% to 95%
Power9 to 36 V DC, dual input; over-voltage, under-voltage, over-current and reverse polarity protection
Interfaces4 × RJ45 2.5 GbE ports, 2 of them with bypass; 2 × 1 GbE SFP ports; RS-232 console
BypassPorts G3 and G4: traffic passed without inspection during a power cut
Vibration10 to 500 Hz, 2 G
Operating systemcOS Core 15.00 or later
Reliability and complianceMTBF of 164,580 hours at 40 °C; CE and FCC Class A

Features from the NetWall 200R Series Getting Started Guide (cOS Core 15.00), checked in November 2026. Performance figures and sector certifications, such as IEC 61850-3 for electrical substations or EN 50121 for railways, are not listed there: we check them against the current datasheet before any recommendation.

What Cyber Praxis does

Expertise in industrial cybersecurity and governance, from diagnosis to investigation.

  • Understand

    • OT/ICS cybersecurity audit
    • Industrial risk analysis
    • IT/OT architecture review
    • Network flow mapping
  • Design

    • Zones and conduits
    • Industrial DMZ
    • Industrial firewall sizing
  • Deploy

    • Clavister installation and configuration
    • Securing remote access
    • Firewall rule review
    • Configuration audit and hardening
  • Operate

    • OT vulnerability management
    • SOC use cases for industry
    • Monitoring and logging
  • Respond

    • Industrial incident response
    • Digital forensics by a registered IT court expert
  • Govern

    • NIS2 support
    • IEC 62443 support

The frameworks, and what each brings

Clavister provides technical measures; implementing them and proving compliance call for an overall approach.

FrameworkWhat it expectsClavister's contributionCyber Praxis's contribution
IEC 62443Zones and conduits, target security levels, system security requirementsImplementing conduits: filtering, protocol control, VPN, logsRisk analysis, zone and conduit design, choice of target levels
NIS2Risk management, network security, incident handling, access controlSegmentation, intrusion prevention, logging, encrypted remote accessGap analysis, action plan, evidence preparation
CyberFundamentals (CCB)Measures by assurance level, including network protection and segmentationImplementing the network measuresSelf-assessment and preparation for verification
ISO/IEC 27001:2022Network security and segregation (controls 8.20 and 8.22), logging and monitoring (8.15 and 8.16)Technical application of these controlsIntegration into the ISMS and the statement of applicability
ISO/IEC 27005Method for managing information security risks—Industrial risk analysis
NIST SP 800-82Guide to operational technology security (revision 3, 2023)Defence in depth and segmentationGood practice reference for the target architecture
Purdue modelLayering from the process (0) to the enterprise (5), with an industrial DMZFirewalls between levelsMapping of the existing set-up and target architecture

We only present a product as IEC 62443 certified on the basis of an official certificate stating its scope. Clavister obtained ISO/IEC 27001 certification in 2025.

Who it is for

In addition to SMEs, mid-sized companies and public administrations, we work in particular with:

  • Critical infrastructure operators
  • Energy suppliers
  • Electricity grid operators
  • Water distribution and treatment
  • Public transport
  • Railway infrastructure
  • Industrial companies
  • Chemical and pharmaceutical industries
  • Port and airport infrastructure
  • Telecommunications
  • Intermunicipal bodies
  • Public bodies covered by NIS2

Frequently asked questions about industrial cybersecurity and Clavister

Is Cyber Praxis a Clavister partner?

Yes. Cyber Praxis is a Clavister partner. We design, install, configure and audit Clavister firewalls in Belgium, particularly for industrial networks and critical infrastructure.

Is Clavister a European sovereign firewall?

Clavister is a Swedish vendor, and its NetWall range is designed and developed in Sweden. The firewalls, their management and their logs can stay entirely on your sites. Sovereignty is nevertheless checked point by point: vendor origin, consoles, logs, cloud services and contract. We document these points for every project.

Can Clavister be deployed fully on-premises, without the cloud?

Largely, yes: InControl or InCenter are installed on your servers, and logs can go to your syslog or your SIEM. Subscription features, such as application control and intrusion prevention, receive their updates from Clavister: we define with you how to deliver them to an isolated network.

Which industrial protocols does Clavister recognise?

The cOS Core 15.00 signature database identifies Modbus, IEC 60870-5-104, OPC UA, EtherNet/IP and CIP, PROFINET, IEC 61850 (GOOSE, MMS), BACnet and S7, among others. DNP3 is not included. Recognising a protocol makes it possible to allow or block it between zones; it is not the same as filtering every command, which we clarify in the study.

Is the Clavister NetWall 200R suitable for an industrial cabinet?

It is designed for it: DIN rail housing, operation from −40 °C to +70 °C, 9 to 36 V DC dual-input power, 2.5 GbE and SFP ports. For an electrical substation or a railway site, we also check the required sector certifications.

What happens during a power cut?

On the NetWall 200R, ports G3 and G4 are then connected directly and pass traffic without inspection: production continues, but without filtering. Depending on your safety and security requirements, we use these ports or not, and we plan a redundant power supply.

Are Clavister products IEC 62443 certified?

We only present a product as IEC 62443 certified on the basis of an official certificate stating its scope, which we check for every project. IEC 62443 applies first to your system: we help you define zones, conduits and security levels, and Clavister firewalls implement part of the technical requirements.

Does production have to stop to install an OT firewall?

Not necessarily. Transparent mode inserts the firewall without changing addressing, and the installation is scheduled in a maintenance window. Every change goes through an impact analysis, validation by the operator and a rollback plan.

How does this help with NIS2?

Segmentation, remote access control, intrusion prevention and logging contribute to the risk management measures of Article 21 of the NIS2 Directive, transposed in Belgium by the Law of 26 April 2024. Compliance remains an overall approach, which we carry out with you, including with CyberFundamentals.